<?xml version="1.0" encoding="UTF-8"?>

<?xml-stylesheet type="text/xsl" href="/static/oaitohtml.xsl"?>

<!--
<?xml-stylesheet type="text/xsl" href="/oaitohtml.xsl"?>
-->

<OAI-PMH xmlns="http://www.openarchives.org/OAI/2.0/" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/ http://www.openarchives.org/OAI/2.0/OAI-PMH.xsd" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance">
    <responseDate>2026-10-13T13:37:13Z</responseDate>
    <request verb="GetRecord" metadataPrefix="oai_dc" identifier="10.57760/sciencedb.hjs.00115" >https://www.scidb.cn/oai</request>
<GetRecord>
    <record>
    <header >
    <identifier>10.57760/sciencedb.hjs.00115</identifier>
    <datestamp>2024-09-25T12:38:48Z</datestamp>
</header>
    <metadata>
        
<oai_dc:dc xmlns:oai_dc="http://www.openarchives.org/OAI/2.0/oai_dc/" xmlns:dc="http://purl.org/dc/elements/1.1/" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.openarchives.org/OAI/2.0/oai_dc/ http://www.openarchives.org/OAI/2.0/oai_dc.xsd">
  <dc:date>2024-09-25</dc:date>
  <dc:title>Design and implementation of a control system for process cooling water with a temperature accuracy of 25&amp;plusmn;0.1℃ based on HC900</dc:title>
  <dc:identifier>doi:10.57760/sciencedb.hjs.00115</dc:identifier>
  <dc:language>en</dc:language>
  <dc:description>&amp;nbsp;[Background]: The electron gun of the Shanghai High Repetition rate XFEL and Extreme light facility (SHINE) needs many necessary conditions to generate high-quality electron bunches. The stability of the temperature of the electron gun body is one of the necessary conditions. [Purpose]: In order to meet the water supply temperature and accuracy of the electron gun system at 25&amp;plusmn;0.1℃, so as to reduce the impact of thermal expansion and deformation on the quality of the electron beam. [Methods]: Based on Honeywell's HC900, a process cooling water control system is designed. The main equipment includes high-precision temperature sensors, high-precision control valves, and three-phase in-line electric heaters. The design scheme is implemented by using advanced PID algorithms and the upper-layer monitoring software EBI. [Results and Conclusions]: After precision testing, this control system has abundant control strategies. The precision of the water supply temperature reaches 25&amp;plusmn;0.1℃, which can meet the current needs of the electron gun.</dc:description>
  <dc:subject>SHINE; HC900; EBI; Process cooling water control system; water temperature control</dc:subject>
  <dc:creator>XIANG Liutang</dc:creator>
  <dc:rights>PUBLIC</dc:rights>
  <dc:rights>https://creativecommons.org/licenses/by/4.0/</dc:rights>
  <dc:type>dataset</dc:type>
  <dc:publisher>Science Data Bank</dc:publisher>
</oai_dc:dc>